34
Power Quality Analyzer Model 8335
WARNING:
Above 104°F (40°C) the instrument can be used only from
the battery or from the battery charger with the battery removed.
It is not recommended to use the battery and charger at the same time.
3.5 Safety Specifications
Electrical Safety
EN 61010-1; 600V CAT IV* (probe dependent - see
§
3.2.5); Pollution Degree 2
Indoor Use
*
Warning
: The assigned voltage and measuring category of the “ current
probe” may differ from the characteristics of the device alone.
•
The use of the AmpFlex
®
, MiniFlex
®
and SR probes rate the “
probe” at
600V CAT IV
or
1000V CAT III.
•
The use of the MR193, MN93, MN193 and SL261 probes rate the
“ current probe” at
300V CAT IV
or
600V CAT III.
• The use of the 5A adapter rates the “ current probe” at
150V
CAT IV
or
300V CAT III.
Electromagnetic Compatibility
Immunity: EN 61326-1:2006
• Resistance to electrostatic discharges (EN 61000-4-2)
1st level : Gravity - 4 kV in contact
Sanctions - CRITERION A
2nd level : Gravity - 8 kV in the air
Sanctions - CRITERION A
• Resistance to radiation (per EN 61000-4-3 and EN 61000-4-8)
Gravity: 10 V.m
-1
Sanctions: CRITERION B (THD
A
altered on Rogowski chain)
• Resistance to rapid transient bursts (EN 61000-4-4)
• Resistance to electric shocks (per EN 61000-4-5)
• Conducted RF interference (per EN 61000-4-6)
• Voltage interruption (per EN 61000-4-11)
Specifications are subject to change without notice.