26
Power Quality Analyzer Model 8335
Measurement
Measurement
range
(with unity ratio)
Resolution
(with unity
ratio)
Accuracy
Min
Max
RMS
Harmonic
Voltage
(order n
≥
2)
Simple
1 V
1200 V
(1)
0.1 V
V < 1000 V
±(2.5 % + 1 V)
1 V
V
≥
1000 V
Compound
1 V
2400 V
(2)
0.1 V
U < 1000 V
±(2.5 % + 1 V)
1 V
U
≥
1000 V
RMS
Harmonic
Current
(order n
≥
2)
SR clamp
MR clamp
1 A
1200 A
0.1 A
A < 1000 A
±(2% + (n x 0.2%) + 1 A)
n
≤
25
1 A
A
≥
1000 A
±(2% + (n x 0.5%) + 1 A)
n > 25
MN93 clamp
0.2 A
240 A
0.1 A
±(2% + (n x 0.2%) + 1 A)
n
≤
25
SL261 clamp
(10mV/A)
MN193 clamp
(100A)
±(2% + (n x 0.5%) + 1 A)
n > 25
0.1 A
120 A
0.01 A
A < 100 A
±(2% + (n x 0.2%) + 0.1 A)
n
≤
25
SL261 clamp
(100mV/A)
0.1 A
A
≥
100 A
±(2% + (n x 0.5%) + 0.1 A)
n > 25
0.01 A
12 A
0.001 A
A < 10 A
±(2% + (n x 0.2%) + 0.01 A)
n
≤
25
MN193 clamp
(5A)
5A adapter
0.01 A
A
≥
10 A
±(2% + (n x 0.5%) + 0.01 A)
n > 25
AmpFlex
®
& MiniFlex
®
0.005 A
6 A
0.001 A
±(2% + (n x 0.2%) + 0.01 A)
n
≤
25
±(2% + (n x 0.5%) + 0.01 A)
n > 25
AmpFlex
®
& MiniFlex
®
10 A
6500 A
0.1 A
A < 1000 A
±(2% + (n x 0.3%) + 1 A +
(Af
rms
(3)
x 0.1%))
n
≤
25
1 A
A
≥
1000 A
±(2% + (n x 0.6%) + 1 A +
(Af
rms
(3)
x 0.1%))
n > 25
(1) In 1000 V
rms
, CAT III, provided that the voltage between each of the terminals and earth does not
exceed 1000 V
rms
.
(2) Two-phase (opposite phases) – same note as (1).
(3) RMS value of the fundamental.