Power Quality Analyzer Model 8335
23
Measurement
Measurement range
without ratio
(with unity ratio)
Resolution
(with unity ratio)
Accuracy
Min
Max
Active
Power
(1)
Excluding
AmpFlex
®
MiniFlex
®
5 mW
(3)
7800 kW
(4)
4 digits at most
(5)
±(1%)
cos
F
≥
0.8
±(1.5% + 10 ct)
0.2
≤
cos
F
< 0.8
AmpFlex
®
MiniFlex
®
±(1%)
cos
F
≥
0.8
±(1.5% + 10 ct)
0.5
≤
cos
F
< 0.8
Reactive
Power
(2)
Excluding
AmpFlex
®
MiniFlex
®
5 mVAR
(3)
7800 kVAR
(4)
4 digits at most
(5)
±(1%)
sin
F
≥
0.5
±(1.5% + 10 ct)
0.2
≤
sin
F
< 0.5
AmpFlex
®
MiniFlex
®
±(1.5%)
sin
F
≥
0.5
±(2.5% + 20 ct)
0.2
≤
sin
F
< 0.5
Apparent Power
5 mVA
(3)
7800 kVA
(4)
4 digits at most
(5)
±(1%)
Peak Factor (PF)
-1
1
0.001
±(1.5%)
cos
F
≥
0.5
±(1.5% + 10 ct)
0.2
≤
cos
F
< 0.8
Active
Energy
(1)
Excluding
AmpFlex
®
MiniFlex
®
1 mWh
9,999,999
MWh
(6)
7 digits at most
(5)
±(1%)
cos
F
≥
0.8
AmpFlex
®
MiniFlex
®
±(1.5%)
0.2
≤
cos
F
< 0.8
±(1%)
cos
F
≥
0.8
±(1.5%)
0.5
≤
cos
F
< 0.8
Reactive
energy
(2)
Excluding
AmpFlex
®
MiniFlex
®
1 mVARh
9,999,999
MVARh
(6)
7 digits at most
(5)
±(1%)
sin
F
≥
0.5
±(1.5%)
0.2
≤
sin
F
< 0.5
AmpFlex
®
MiniFlex
®
±(1.5%)
sin
F
≥
0.5
±(2%)
0.2
≤
sin
F
< 0.5