24
Power Quality Analyzer Model 8335
Apparent energy
1 mVAh
9,999,999
MVAh
(6)
7 digits at most
(5)
±(1%)
(1) The stated uncertainties on the active power and energy measurements are max for |cos
F|
= 1 and
typical for the other phase differences.
(2) The stated uncertainties on the reactive power and energy measurements are max for |sin
F|
= 1
and typical for the other phase shifts.
(3) With MN193 clamp (5A) or 5A adapter.
(4) With AmpFlex
®
or MiniFlex
®
.
(5) The resolution depends on the current sensor used and on the value to be displayed.
(6) The energy is equivalent to more than 146 years of the associated maximum power (unity ratios).
Measurement
Measurement Range
Resolution
Accuracy
Min
Max
Phase differences
of fundamentals
-179°
180°
1°
±(2°)
cos
F
(DPF)
-1
1
0.001
±(1°) for
F
±(5 ct) for DPF
tan F
-32.77
(1)
32.77
(1)
0.001
tan
F
< 10
±(1°) for
F
0.01
tan
F
≥
10
Unbalance
(UNB)
0%
100%
0.1%
±(1%)
(1)
|
tan
F|
= 32,767 corresponds to
F
= ±88.25° + k × 180° (k being a natural number)
Measurement
Measurement Range
Resolution
Accuracy
Min
Max
Voltage Harmonic
Ratio (t)
0%
1600%
0.1%
t
< 999.9%
±(2.5 % + 5 ct)
1%
t
≥
1000%
Current Harmonic
Ratio (t)
(excluding
AmpFlex
®
& MiniFlex
®
)
0%
1600%
0.1%
t
< 999.9%
±(2% + (n × 0.2%) + 5 ct)
n
≤
25
1%
t
≥
1000%
±(2% + (n × 0.5%) + 5 ct)
n > 25
Current Harmonic
Ratio (t)
(AmpFlex
®
& MiniFlex
®
)
0%
1600%
0.1%
t
< 999.9%
±(2% + (n × 0.3%) + 5 ct)
n
≤
25
1%
t
≥
1000%
±(2% + (n × 0.6%) + 5 ct)
n > 25
Total Voltage
Harmonic Distortion
THD (THD-F)
0%
999.9%
0.1%
±(2.5% + 5 ct)