Power Quality Analyzer Model 8335
119
Powers
(excluding neutral – over one second)
NSS =
number of samples in a second
Active power of phase (i+1) with i
∈
[0 ; 2].
[ ]
[ ][ ] [ ][ ]
∑
−
=
⋅
⋅
=
1
0
1
W
NSS
n
n
i
A
n
i
V
NSS
i
Apparent power of phase (i+1) with i
∈
[0 ; 2].
Reactive power (without harmonics) of phase (i+1) with i
∈
[0 ; 2].
[]
[][ ]
i
VAR
NSS-1
0
n
VF
AF i
n
.
.
∑
=
[]
]
[
n
i
=
-
1
NSS
NSC
4
Reactive power (with harmonics) of phase (i+1) with i
∈
[0 ; 2].
Reactive powers are calculated using the filtered signals (without harmonics) –
VF[i][j] and AF[i][j] - in accordance with EDF (French national electricity company)
rules or from the apparent and active powers (with harmonics). The choice of cal
-
culation is left up to the user.
Total active power
W[3] = W[0] + W[1] + W[2]
Total apparent power
VA[3] = VA[0] + VA[1] + VA[2]
Total reactive power
VAR[3] = VAR[0] + VAR[1] + VAR[2]
Power ratios
(excluding neutral – over one second)
NSS =
number of samples in a second
Power Factor of phase (i+1) with i
∈
[0 ; 2].