Power Quality Analyzer Model 8335
37
4.3 Instrument Configuration
(Set-up mode)
NOTE:
All configurations can be modified through DataView
®
software also.
The instrument must be configured the first time it is used. The configu-
ration is saved in memory when the instrument is turned OFF.
Press the
button to configure the unit. The following sub-menus appear:
Figure 4-2
•
Set the display language by pressing the yellow button corresponding to the
screen language icons.
•
The parameter that is ready to be configured will be highlighted in yellow. To
move to a different parameter, use the
▲ and ▼ buttons.
•
Press the Enter button to select a parameter.
•
Use the ◄ and ► buttons to change a value or setting.
•
When finished, return to the Configuration menu by pressing the
button.
PARAMETER
FUNCTION
Date / Time
Sets the date and time format (see § 4.3.1)
Display
Adjusts the contrast and brightness of the display;
Defines the color of the voltage and current curves (see § 4.3.2)
Calculation Methods
Determines if harmonics are used or not used in calculations of
reactive quantities (power and energy) - (see § 4.3.3)
-
With harmonics:
Harmonics are taken into account when
calculating reactive parameters.
-
Without harmonics:
Only the fundamental part is used for
the calculation of reactive parameters
Electrical Connection
Determines the type of connection to the network (see § 4.3.4)
•
Single-Phase
•
Split-Phase
•
3-Phase 4-Wire
•
3-Phase 5-Wire