Power Quality Analyzer Model 8335
RMS ½
current
SR clamp
MR clamp
1 A
1200 A
0.1 A
A < 1000 A
±(1% + 1 A)
1 A
A
≥
1000 A
MN93 clamp
0.2 A
240 A
0.1 A
±(1% + 1 A)
SL261 clamp
(10mV/A)
MN93A clamp
(100A)
0.1A
120 A
0.01 A
A < 100 A
±(1% + 0.1 A)
0.1 A
A
≥
100 A
SL261 clamp
(100mV/A)
0.01 A
12 A
0.001 A
A < 10 A
±(1% + 0.01 A)
0.01 A
A
≥
10 A
MN193 clamp (5A)
5A adapter
0.005 A
6 A
0.001 A
±(1% + 0.01 A)
AmpFlex
®
MiniFlex
®
10 A
6500 A
0.1 A
A < 1000 A
±(1.5% + 5 A)
1 A
A
≥
1000 A
Peak
Current
SR clamp
MR clamp
1 A
1697 A
(3)
1 A
A < 1000 A
±(1% + 1 A)
1 A
A
≥
1000 A
MN93 clamp
0.2 A
339.4 A
(3)
0.1 A
±(1% + 1 A)
SL261 clamp
(10mV/A)
MN193 clamp
(100A)
0.1 A
169.7 A
(3)
0.01 A
A < 100 A
±(1% + 0.1 A)
0.1 A
A
≥
100 A
SL261 clamp
(100mV/A)
0.01 A
16.97 A
(3)
0.001 A
A < 10 A
±(1% + 0.01 A)
0.01 A
A
≥
10 A
MN193 clamp (5A)
5A adapter
0.005 A
8.485 A
(3)
0.001 A
±(1% + 0.01 A)
AmpFlex
®
MiniFlex
®
10 A
9192 A
(3)
0.1 A
A < 1000 A
±(1.5% + 5 A)
1 A
A
≥
1000 A
Severity of flicker (Pst)
0
12
0.01
See the
corresponding table
(1) In 1000 Vrms, CAT III, provided that the voltage between each of the terminals and earth does not
exceed 1000 Vrms
(2) Two-phase (opposite phases) – same note as (1)
(3) 1200 x
√
2
≈
1697; 2400 x
√
2
≈
3394; 240 x
√
2
≈
339,4; 120 x
√
2
≈
169,7; 12 x
√
2
≈
16,97; 6 x
√
2
≈
8,485; 6500 x
√
2
≈
9192