Standard function blocks
294
Operation
The output (Q) is set to 1 when the input (IN) has been 1 for a time defined by the pulse
time input (PT). The output is set to 0, when the input is set to 0.
Elapsed time count (TE) starts when the input is set to 1 and stops when the input is set
to 0.
Example:
Inputs
Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs
Output (Q): Boolean
Elapsed time output (ET): DINT (1 = 1 µs)
TP
(10060)
Illustration
Execution time
1.46 µs
Operation
The output (Q) is set to 1 when the input (IN) is set to 1. The output is set to 0, when it
has been 1 for a time defined by the pulse time input (PT).
Elapsed time count (TE) starts when the input is set to 1 and stops when the input is set
to 0.
Inputs
Input (IN): Boolean
Pulse time input (PT): DINT (1 = 1 µs)
Outputs
Output (Q): Boolean
Elapsed time output (ET): DINT (1 = 1 µs)
IN
Q
PT
PT
ET
ET
ET
TP
88
TLA1 1 msec
(1)
PT
>IN
Q
Q(88)
ET
ET(88)
IN
Q
ET
PT
PT
PT