Standard function blocks
286
Operation
Reads the internal (non-scaled) value of the source of a pointer parameter. The pointer
parameter is specified using the Group and Index inputs.
The value of the source selected by the pointer parameter is provided by the Output pin.
Error codes are indicated by the error output (Error) as follows:
Inputs
Parameter group (Group): DINT
Parameter index (Index): DINT
Outputs
Output (Output): Boolean, INT, DINT, REAL, REAL24
Error output (Error): DINT
PARWR
(10080)
Illustration
Execution time
14.50 µs
Operation
The input value (IN) is written to the defined parameter (Group and Index).
The new parameter value is stored to the flash memory if the store input (Store) is 1.
Note:
Cyclic parameter value storing can damage the memory unit. Parameter values
should be stored only when necessary.
Error codes are indicated by the error output (Error) as follows:
Inputs
Input (IN): DINT
Parameter group input (Group): DINT
Parameter index input (Index): DINT
Store input (Store): Boolean
Outputs
Error output (Error): DINT
Error code
Description
0
No error or busy
≠
0
Error
PARWR
75
TLA1 1 msec
(1)
IN
Group
Index
Store
Error
Error(75)
Error code
Description
0
No error
< >
0
Error
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......