Parameters and firmware blocks
138
Group
Settings for thermal protection of the motor. See also section
on page
.
45
45 MOT THERM PROT
Firmware block:
MOT THERM PROT
(45)
Configures motor overtemperature
protection and temperature
measurement. Also shows the
estimated and measured motor
temperatures.
Block outputs located in other
parameter groups
(page
)
(page
)
45.01
MOT TEMP PROT
FW block:
(see above)
Selects how the drive reacts when motor overtemperature is detected.
(0)
NO
Inactive.
(1)
ALARM
The drive generates alarm MOTOR TEMPERATURE when the
temperature exceeds the alarm level defined by parameter
MOT TEMP ALM LIM.
(2)
FAULT
The drive generates alarm MOTOR TEMPERATURE or trips on fault
MOTOR OVERTEMP when the temperature exceeds the alarm/fault
level defined by parameter
45.02
MOT TEMP SOURCE
FW block:
(see above)
Selects the motor temperature protection. When overtemperature is detected the drive reacts as
defined by parameter
.
MOT THERM PROT
32
TLF11 10 msec
(5)
45.01 MOT TEMP PROT
[ No ]
45.02 MOT TEMP SOURCE
[ ESTIMATED ]
45.03 MOT TEMP ALM LIM
[ 90 C ]
45.04 MOT TEMP FLT LIM
[ 110 C ]
45.05 AMBIENT TEMP
[ 20 C ]
45.06 MOT LOAD CURVE
[ 100 % ]
45.07 ZERO SPEED LOAD
[ 100 % ]
45.08 BREAK POINT
[ 45.00 Hz ]
45.09 MOTNOMTEMPRISE
[ 80 C ]
45.10 MOT THERM TIME
[ 256 s ]
1.17 MOTOR TEMP
1.18 MOTOR TEMP EST
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......