Parameters and firmware blocks
180
99.08
MOT NOM FREQ
FW block: None
Defines the nominal motor frequency.
Note:
This parameter cannot be changed while the drive is running.
5…500 Hz
Nominal motor frequency.
99.09
MOT NOM SPEED
FW block: None
Defines the nominal motor speed. Must be equal to the value on the motor rating plate. When
parameter value is changed, check the speed limits in parameter group
Note:
This parameter cannot be changed while the drive is running.
0…30000 rpm
Nominal motor speed.
99.10
MOT NOM POWER
FW block: None
Defines the nominal motor power. Must be equal to the value on the motor rating plate. If several
motors are connected to the inverter, enter the total power of the motors. Set also parameter
.
Note:
This parameter cannot be changed while the drive is running.
0…10000 kW
Nominal motor power.
99.11
MOT NOM COSFII
FW block: None
Defines the cosphi (not applicable to permanent magnet motors) for a more accurate motor model.
Not obligatory; if set, should be equal to the value on the motor rating plate.
Note:
This parameter cannot be changed while the drive is running.
0…1
Cosphi (0 = parameter disabled).
99.12
MOT NOM TORQUE
FW block: None
Defines the nominal motor shaft torque for a more accurate motor model. Not obligatory.
Note:
This parameter cannot be changed while the drive is running.
0…2147483 Nm
Nominal motor shaft torque.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......