Standard function blocks
265
The AIx filt gain inputs determine a filtering time for each input as follows:
The AIx mode outputs show whether the corresponding input is voltage (0) or current
(1). The voltage/current selection is made using the hardware switches on the FIO-11.
Inputs
Analogue input filter gain selection (AI1 filt gain … AI3 filt gain): INT
Minimum value of input signal (AI1 Min … AI3 Min): REAL (> -11 V or -22 mA)
Maximum value of input signal (AI1 Max … AI3 Max): REAL (< 11 V or 22 mA)
Minimum value of scaled output signal (AI1 Min scale … AI3 Min scale): REAL
Maximum value of scaled output signal (AI1 Max scale … AI3 Max scale): REAL
Outputs
Analogue input mode (voltage or current) (AI1 mode … AI3 mode): Boolean
Value of analogue input (AI1 … AI3): REAL
Scaled value of analogue input (AI1 scaled … AI3 scaled): REAL
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
AIx scaled
32768
AIx [V or mA]
11 V or
-11 V or
AI
x Max
AI
x Mi
n
AIx Min Scale
AIx Max Scale
-22 mA
22 mA
AIx Min Scale > AIx Max Scale
-32768
AIx filt gain
Filtering time
Notes
0
No filtering
1
125 µs
Recommended setting
2
250 µs
3
500 µs
4
1 ms
5
2 ms
6
4 ms
7
7.9375 ms
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......