Parameters and firmware blocks
141
45.09
MOTNOMTEMPRISE
(see above)
Defines the temperature rise of the motor when the motor is loaded with nominal current. See the
motor manufacturer's recommendations.
The temperature rise value is used by the motor thermal protection model when parameter
is set to
.
0…300 °C
Motor temperature rise.
45.10
MOT THERM TIME
(see above)
Defines the thermal time constant for the motor thermal protection model (i.e. time inside which the
temperature has reached 63% of the nominal temperature). See the motor manufacturer's
recommendations.
The motor thermal protection model is used when parameter
is set to
.
100…10000 s
Motor thermal time.
t
Temperature
Ambient temperature
Motor nominal
temperature rise
Motor
100%
Temp.
63%
Motor thermal time
t
t
100%
load
rise
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......