Start-up
17
Motor data entering
Open the parameter and signal list by selecting the Parameter
Browser of the appropriate drive.
Select the language.
Parameters are set as follows:
Select the parameter group (in this case 99 START-UP DATA) by
double-clicking it. Select the appropriate parameter by double-clicking
it and set the new value.
Select the motor type: asynchronous or permanent magnet motor.
Select the motor control mode. DTC is suitable for most cases. For
information on scalar control, see parameter
.
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
Permanent magnet motor nameplate example:
Note:
Set the motor data
to exactly the same value
as on the motor
nameplate. For example,
if the motor nominal
speed is 1470 rpm on the
nameplate, setting the
value of parameter
to
1500 rpm results in
wrong operation of the
drive.
With DTC control (
) at least
…
must be set. Better control accuracy can be
achieved by setting also parameters
…
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C3
6312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz
kW
r/min
A
cos
IA/IN t E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors
380 V
mains
voltage
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......