Fault tracing
214
0040
ENCODER2
(0x7381)
Encoder 2 feedback fault
See fault ENCODER1.
EnDat or SSI encoder is used in
continuous mode as encoder 2.
[I.e.
and
and
=
=
).]
If possible, use single position transfer
instead of continuous position transfer (i.e. if
encoder has incremental sin/cos signals):
- Change parameter
/
Otherwise use Endat/SSI encoder as
encoder 1:
- Change parameter
to value
and parameter
to value
Note:
The new setting will only take effect
after parameter
used or after the JCU control unit is powered
up the next time.
0045
FIELDBUS COMM
(0x7510)
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module or between
PLC and fieldbus adapter
module is lost.
Check status of fieldbus communication. See
appropriate User’s Manual of fieldbus adapter
module.
Check fieldbus parameter settings. See
parameter group
.
Check cable connections.
Check if communication master can
communicate.
0046
FB MAPPING FILE
(0x6306)
Drive internal fault
Contact your local ABB representative.
0047
MOTOR OVERTEMP
(0x4310)
Programmable fault:
Estimated motor temperature
(based on motor thermal model)
has exceeded fault limit defined
by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
Check motor thermal model settings,
parameters
and
Measured motor temperature
has exceeded fault limit defined
by parameter
.
Check that actual number of sensors
corresponds to value set by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
0049
AI SUPERVISION
(0x8110)
Programmable fault:
Analogue input AI1 or AI2 signal
has reached limit defined by
parameter
Check analogue input AI1/2 source and
connections.
Check analogue input AI1/2 minimum and
maximum limit settings, parameters
and
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......