Parameters and firmware blocks
139
(0)
ESTIMATED
The temperature is supervised based on the motor thermal protection
model, which uses the motor thermal time constant (parameter
) and the motor load curve (parameters
). User tuning is typically needed only if the ambient
temperature differs from the normal operating temperature specified
for the motor.
The motor temperature increases if it operates in the region above the
motor load curve. The motor temperature decreases if it operates in
the region below the motor load curve (if the motor is overheated).
WARNING!
The model does not protect the motor if it does not
cool properly due to dust and dirt.
(1)
KTY JCU
The temperature is supervised using a KTY84 sensor connected to
drive thermistor input TH.
(2)
KTY 1st FEN
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision.
Note:
This selection
does not apply for FEN-01. *
(3)
KTY 2nd FEN
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision.
Note:
This selection
does not apply for FEN-01. *
(4)
PTC JCU
The temperature is supervised using 1…3 PTC sensors connected to
drive thermistor input TH.
(5)
PTC 1st FEN
The temperature is supervised using a PTC sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. *
(6)
PTC 2nd FEN
The temperature is supervised using a PTC sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. *
*Note:
If one FEN-xx module is used, parameter setting must be either
. The FEN-xx module can be in either Slot 1 or Slot 2.
45.03
MOT TEMP ALM LIM
(see above)
Defines the alarm limit for the motor overtemperature protection (when par.
=
).
0…200 °C
Motor overtemperature alarm limit.
45.04
MOT TEMP FLT LIM
(see above)
Defines the fault limit for the motor overtemperature protection (when par.
MOT TEMP PROT =
).
0…200 °C
Motor overtemperature fault limit.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......