12-40 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
USER STATUS WORD 1 BIT 7
SEL
(06.67)
Default: Identification run done (2)
Range: 0 - 2, Other
False
0
True 1
Identification run done 2 - Bit 0 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 7 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 8
SEL
(06.68)
Default: Start inhibition (2)
Range: 0 - 2, Other
False
0
True 1
Start inhibition 2 - Bit 7 of 06.18 Start inhibit status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 8 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 9
SEL
(06.69)
Default: Limiting (2)
Range: 0 - 2, Other
False
0
True 1
Limiting 2 - Bit 7 of 06.16 Drive status word 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 9 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 10
SEL
(06.70)
Default: Limiting (2)
Range: 0 - 2, Other
False
0
True 1
Limiting 2 - Bit 2 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 9 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 11
SEL
(06.71)
Default: Zero speed (2)
Range: 0 - 2, Other
False
0
True 1
Limiting 2 - Bit 0 of 06.19 Speed control status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 11 of 06.50 User
status word 1.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...