4-2 Terminal Specifications
3AXD50000011888
Catalog Number
ACS880-01-
Frame Size
Metric
1)
US
2)
Cu Cable
Type Typical
AI Cable
Type Typical
Cu Cable
Type Typical
AI Cable
Type Typical
mm
2
mm
2
AWG/kcmil
AWG/kcmil
440…480V
02A1-5+N5350
R1
3 x 1.5
-
14
-
03A0-5+N5350
R1
3 x 1.5
-
14
-
03A4-5+N5350
R1
3 x 1.5
-
14
-
04A8-5+N5350
R1
3 x 1.5
-
14
-
05A2-5+N5350
R1
3 x 1.5
-
14
-
07A6-5+N5350
R1
3 x 1.5
-
14
-
11A0-5+N5350
R1
3 x 1.5
-
14
-
014A-5+N5350
R2
3 x 6
-
10
-
021A-5+N5350
R2
3 x 6
-
10
-
027A-5+N5350
R3
3 x 10
-
8
-
034A-5+N5350
R3
3 x 6
-
8
-
040A-5+N5350
R4
3 x 16
3 x 25
6
-
052A-5+N5350
R4
3 x 25
3 x 25
4
-
065A-5+N5350
R5
3 x 35
3 x 35
3
-
077A-5+N5350
R5
3 x 35
3 x 50
3
-
096A-5+N5350
R6
3 x 50
3 x 70
1
-
124A-5+N5350
R6
3 x 95
3 x 95
2/0
-
156A-5+N5350
R7
3 x 120
3 x 150
3/0
-
180A-5+N5350
R7
3 x 150
3 x 185
250 MCM
-
240A-5+N5350
R8
2 x (3x70)
3)
2 x (3x95)
300 MCM
-
260A-5+N5350
R8
2 x (3x70)
3)
2 x (3x95)
2 x 3/0
-
302A-5+N5350
R9
2 x (3x95)
2 x (3x120)
2 x 3/0
-
361A-5+N5350
R9
2 x (3x120)
2 x (3x185)
2 x 250 MCM
-
414A-5+N5350
R9
2 x (3x150)
2 x (3x240)
2 x 250 MCM
-
660…690V
07A3-7+N5350
R5
3 x 1.5
-
14
12
09A8-7+N5350
R5
3 x 1.5
-
14
12
14A2-7+N5350
R5
3 x 2.5
-
14
12
018A-7+N5350
R5
3 x 4
-
12
10
022A-7+N5350
R5
3 x 6
-
10
8
026A-7+N5350
R5
3 x 10
3 x 25
8
6
035A-7+N5350
R5
3 x 10
3 x 25
8
6
042A-7+N5350
R5
3 x 16
3 x 25
6
4
049A-7+N5350
R5
3 x 16
3 x 25
6
4
061A-7+N5350
R6
3 x 25
3 x 35
4
3
084A-7+N5350
R6
3 x 35
3 x 50
3
2
098A-7+N5350
R7
3 x 50
3 x 70
2
1/0
119A-7+N5350
R7
3 x 70
3 x 95
1/0
3/0
142A-7+N5350
R8
3 x 95
3)
3 x 120
2/0
4/0
174A-7+N5350
R8
3 x 120
3)
2 x (3x70)
4/0
300 MCM
210A-7+N5350
R9
3 x 185
2 x (3x95)
300 MCM
2 x 3/0
271A-7+N5350
R9
3 x 240
2 x (3x120)
400 MCM
2 x 4/0
Table 4-1 Power Wire Gauge Specification (Cont.)
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...