12-4 Startup Assistant & Parameters
3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
Highlight the desired unit with the and press
(next).
Use to move between the units. Use to
select the value for editing.
Pressing
(save) returns to the unit selection
menu.
Unit Selection
Tariff currency unit
AI1 unit selection
00:00
Next
Back
CTDD
0.0 rpm
Local
Units
Change the display units if needed.
0000 0000 0001 00011
USD
V
Supply Voltage Settings
Press to edit the supply voltage input to the
CTDD drive.
Note:
For 460...480 V, it is recommended that supply
voltage is set to 500 V.
Supply voltage
00:00
Next
Back
CTDD
0.0 rpm
Local
Supply voltage
Set supply voltage.
500 V
Motor Data Settings
Refer to the motor nameplate for the following parameter settings. Whenever possible, enter the values exactly as
shown on the motor nameplate.
Example of a nameplate of a Back-EMF motor:
MEASURED OPEN CIRCUIT VOLTAGE
IS
VOLTS AT
RPM.
MOTOR PHASE CURRENT SHOULD NOT
EXCEED
AMPS RMS PEAK TO
AVOID DEMAGNETIZATION.
000692-000VY
PERMANENT MAGNET MOTOR
WHEN SHAFT IS ROTATED, VOLTAGE WILL BE
GENERATED AT THE MOTOR TERMINALS.
WARNING
patent US 7,385,328
Example of a nameplate of a permanent magnet motor:
000613-006AAP
DUTY
HP
RPM
AMPS
VOLTS
HZ
PLANT 15
ENCL. MOD.
SER. NO.
S.F.
DESIGN NO.
PH.
D.E.
BRG.
O.D.E.
BRG.
MAX. SAFE
AMB.
MIN. AMB.
°C
°C
FR.
INSUL
ENCL.
SPEED
TYPE
MINIMUM AIRFLOW VELOCITY FT. PER MINUTE
PATENT US 7,880,348 B2
CAT
NO.
SPEC
NO.
LR40567
C
US
R
TM
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...