12-70 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
FAULT
FUNCTIONS
(Continued)
EXTERNAL EVENT 1 TYPE
(31.02)
Default: 0 (Fault)
Range: 0, 1, 3
0 (Fault) The external event generates a fault.
1 (Warning) The external event generates a warning.
3 (Warning/Fault) If the drive is modulating, the external event generates a fault.
Otherwise, the event generates a warning.
Selects the type of external event 1.
FAULT RESET SELECTION
(31.11)
Default: 4 (DI3)
Range: 0 - 7, 10, 11, 30, 32, Other
Not selected 0
Selected
1
2 (DI1)
Digital input DI1 (10.02 DI delayed status, bit 0)
3 (DI2)
Digital input DI2 (10.02 DI delayed status, bit 1)
4 (DI3)
Digital input DI3 (10.02 DI delayed status, bit 2)
5 (DI4) Digital input DI4 (10.02 DI delayed status, bit 3)
6 (DI5) Digital input DI5 (10.02 DI delayed status, bit 4)
7 (DI6) Digital input DI6 (10.02 DI delayed status, bit 5)
10 (DIO1) Digital input/output DIO1 (11.02 DIO delayed status, bit 0)
11 (DIO2) Digital input/output DIO2 (11.02 DIO delayed status, bit 1)
30 (FBA A MCW bit 7) Control word bit 7 received through fieldbus interface A
32 (EFB MCW bit 7) Control word bit 7 received through the embedded fieldbus interface
Other [bit]
Source selection (see Terms and abbreviations)
Selects the source of an external fault reset signal. The signal resets
the drive after a fault trip if the cause of the fault no longer exists.
0 –> 1 = Reset
Note:
A fault reset from the fieldbus interface is always observed
regardless of this parameter.
USER SELECTABLE FAULT
(31.13)
Default: 0000h
Range: 0000h to FFFFh
Defines the fault that can be automatically reset using parameter 31.12
Autoreset selection, bit 10. The faults are listed in chapter Fault
tracing.
NUMBER OF TRIALS
(31.14)
Default: 0
Range: 0 - 5
Defines the maximum number of automatic resets that the drive is
allowed to attempt within the time specified by 31.15 Total trials time.
If the fault persists, subsequent reset attempts will be made at
intervals defined by 31.16 Delay time.
The faults to be automatically reset are defined by 31.12 Autoreset
selection.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...