Startup Assistant & Parameters 12-81
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
EMBEDDED
FIELDBUS
(Continued)
EFB REF1 TYPE
(58.26)
Default: 0 (Auto)
Range: 0 - 5
0 (ABB Drives)
Type and scaling are chosen automatically according to which
reference chain (see settings Torque, Speed, Frequency) the incoming
reference is connected to. If the reference is not connected to any
chain, no scaling is applied (as with setting Transparent).
2 (Transparent)
No scaling is applied.
2 (General)
Generic reference with a scaling of 100 = 1 (ie. integer and two
decimals).
3 (Torque) The scaling is defined by parameter 46.03 Torque scaling.
4 (Speed) The scaling is defined by parameter 46.01 Speed scaling.
5 (Frequency) The scaling is defined by parameter 46.02 Frequency scaling.
Selects the type and scaling of reference 1 received through the
embedded fieldbus interface.
The scaled reference is displayed by 03.09 EFB reference 1.
EFB REF2 TYPE
(58.27)
Default: 3 (Torque)
Range: 0 - 5
Selects the type and scaling of reference 2 received through the
embedded fieldbus interface.
The scaled reference is displayed by 03.10 EFB reference 2.
For the selections, see parameter 58.26 EFB ref1 type.
EFB ACT1 TYPE
(58.28)
Default: 0 (Auto)
Range: 0 - 6
0 (Auto)
Type/source and scaling follow the type of reference 1 selected by
parameter 58.26 EFB ref1 type. See the individual settings below for
the sources and scalings.
1 (Transparent)
The value selected by parameter 58.31 EFB act1 transparent source is
sent as actual value 1. No scaling is applied (the 16-bit scaling is 1 = 1
unit).
2 (General)
The value selected by parameter 58.31 EFB act1 transparent source is
sent as actual value 1 with a 16-bit scaling of 100 = 1 unit (ie. integer
and two decimals).
3 (Torque) 01.10 Motor torque is sent as actual value 1. The scaling is defined by
parameter 46.03 Torque scaling.
4 (Speed) 01.01 Motor speed used is sent as actual value 1. The scaling is
defined by parameter 46.01 Speed scaling.
5 (Frequency) 01.06 Output frequency is sent as actual value 1. The scaling is
defined by parameter 46.02 Frequency scaling.
6 (Position) Motor position is sent as actual value 1. See parameter 90.06 Motor
position scaled.
Selects the type/source and scaling of actual value 1 transmitted to the
fieldbus network through the embedded fieldbus interface.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...