13-8 Troubleshooting
3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text)
Warning
Fault #
Cause
What to do
Edge counter 2
(Editable message text)
Programmable warning:
33.45 Edge counter 2
warn message
A889
Warning generated by
edge counter 2.
Check the source of the warning (parameter 33.43 Edge
counter 2 source).
Value counter 1
(Editable message text)
Programmable warning:
33.55 Value counter 1
warn message
A88A
Warning generated by
value counter 1.
Check the source of the warning (parameter 33.53 Value
counter 1 source).
Value counter 2
(Editable message text)
Programmable warning:
33.65 Value counter 2
warn message
A88B
Warning generated by
value counter 2.
Check the source of the warning (parameter 33.63 Value
counter 2 source).
Device clean
A88C
Warning generated by an
ontime timer.
Programmable warnings:
33.14 On-time 1
warn message
33.24 On-time 2
warn message
Check the event log for an auxiliary code.
Check the source of the warning corresponding to the
code:
0: 33.13 On-time 1 source
1: 33.23 On-time 2 source
10: 05.04 Fan on-time counter.
DC capacitor
A88D
Cabinet fan
A88E
Cooling fan
A88F
Additional cooling
A890
AI supervision
Programmable warning:
12.03 AI supervision
function
A8A0
An analog signal is outside
the limits specified for the
analog input.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits of the input in
parameter group 12 Standard AI.
Signal supervision
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
32.16 Supervision 2 action
32.26 Supervision 3 action
A8B0
Warning generated by
a signal supervision
function.
Check the source of the warning (parameter 32.07, 32.17
or 32.28).
External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1 source
31.02 External event 1 type
A981
Fault in external device 1.
Check the external device.
Check setting of parameter 31.01 External event 1
source.
External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2 source
31.04 External event 2 type
A982
Fault in external device 2.
Check the external device.
Check setting of parameter 31.03 External event 2
source.
External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3 source
31.06 External event 3 type
A983
Fault in external device 3.
Check the external device.
Check setting of parameter 31.05 External event 3
source.
External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4 source
31.08 External event 4 type
A984
Fault in external device 4.
Check the external device.
Check setting of parameter 31.07 External event 4
source.
External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5 source
31.10 External event 5 type
A985
Fault in external device 5.
Check the external device.
Check setting of parameter 31.09 External event 5
source.
FA2FA DDCS com
loss
Programmable warning:
60.79 INU-LSU com loss ctrl
AF80
DDCS (fiber optic)
communication between
converters (for example,
the inverter unit and the
supply unit) is lost.
Check status of other converter (parameters 06.36 and
06.39).
Check settings of parameter group 60 DDCS
communication. Check the corresponding settings in the
control program of the other converter.
Check cable connections. If necessary, replace cables.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...