Startup Assistant & Parameters 12-7
3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
The ID run in progress screen will automatically
display showing speed and amps.
The screen will also indicate if an ID run has been
completed before. If not, it will read “none”. If a run
has been completed, it will read “Standstill”.
CTDD
50.0 rpm
Local
ID run in progress...
00:00
Back
01.01 Motor speed used
01.07 Motor current
0.00 rpm
0.00 A
99.14 Last ID run performed
None
When ID run is complete, the next screen will be
displayed.
CTDD
50.0 rpm
Local
ID run in progress...
00:00
Exit
01.01 Motor speed used
01.07 Motor current
0.00 rpm
0.00 A
99.14 Last ID run performed
None
ID run done
√
NOTE:
If the motor data is incorrect, after pressing
,
the display will indicate check motor parameters.
Press
(exit) and check that the motor information
is correct.
00:00
Check params
Exit
CTDD
0.0 rpm
Local
Check the motor param...
The motor parameters are probably
set incorrectly. Check the parameters.