Startup Assistant & Parameters 12-35
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
INTERNAL STATE MACHINE
LSU CW
(06.39)
Default:
Read Only
Range: 0000h - FFFFh
(Only visible with a BCU control unit) Shows the control word sent
to the supply unit from the INULSU (inverter unit/supply unit) state
machine. This parameter is read-only.
Bit
Name
Descriptions
0
ON/OFF
1 = Start charging
0 = Open main contactor (switch power
off)
1
OFF 2
0 = Emergency stop (Off2)
2
OFF 3
0 = Emergency stop (Off3)
3
START
1 = Start modulating
0 = Stop modulating
4-6
Reserved
7
RESET
0 -> 1 = Reset an active fault - A fresh
start command is required after reset
8-11
Reserved
12
USER BIT 0
See parameter 06.40 LSU CW user bit 0
selection
13
USER BIT 1
See parameter 06.41 LSU CW user bit 1
selection
14
USER BIT 2
See parameter 06.42 LSU CW user bit 2
selection
15
USER BIT 3
See parameter 06.43 LSU CW user bit 3
selection
LSU CW USER BIT 0
SELECTION
(06.40)
Default: MCW user bit 0 (2)
Range: 0 - 5, Other
False (0)
0
True (1)
1
MCW user bit 0 (2)
Bit 12 of 06.01 Main control word
MCW user bit 1 (3)
Bit 13 of 06.01 Main control word
MCW user bit 2 (4)
Bit 14 of 06.01 Main control word
MCW user bit 3 (5)
Bit 15 of 06.01 Main control word
Other [bit]
Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit)
Selects a binary source whose status is transmitted as bit 12 of 06.39
Internal state machine LSU CW to the supply unit.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...