![ABB ACS880+N5350 User Manual Download Page 112](http://html.mh-extra.com/html/abb/acs880-n5350/acs880-n5350_user-manual_3307112.webp)
Startup Assistant & Parameters 12-33
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
SPEED SPEED STATUS
WORD
(06.20)
Default:
Read Only
Range: 0000h - FFFFh
Constant speed/frequency status word. Indicates which constant
speed or frequency is active (if any). See also parameter 06.19 Speed
control status word, bit 7, and section Constant speeds/frequencies.
This parameter is read-only.
Bit
Name
Descriptions
0
Constant speed 1 1 = Constant speed or frequency 1 selected
1
Constant speed 2 1 = Constant speed or frequency 2 selected
2
Constant speed 3 1 = Constant speed or frequency 3 selected
3
Constant speed 4 1 = Constant speed or frequency 4 selected
4
Constant speed 5 1 = Constant speed or frequency 5 selected
5
Constant speed 6 1 = Constant speed or frequency 6 selected
6
Constant speed 7 1 = Constant speed or frequency 7 selected
7 - 15 Reserved
CONSTANT SPEED STATUS
WORD
(06.25)
Default:
Read Only
Range: 0000h - FFFFh
Drive inhibit status word 2. This word specifies the source of the
inhibiting signal that is preventing the drive from starting.
See also parameter 06.18 Start inhibit status word, and 06.16 Drive
status word 1, bit 1.
This parameter is read-only.
Bit
Name
Descriptions
0
Follower drive
1 = A follower is preventing the master from
starting
1
Application
1 = The application program is preventing
the drive from starting
2
Aux. power failure 1 = A control unit auxiliary power failure is
preventing the drive from starting
3
Encoder
feedback
1 = The encoder feedback configuration is
preventing the drive from starting
4
Ref source
parametrization
1 = A reference source parametrization
conflict is preventing the drive from starting.
See warning A6DA Reference source
parametrization
5 - 15 Reserved
MSW BIT 14 SEL (06.33)
Default: False (0)
Range: 0, 1, Other
False
0
True
1
Other [bit]
Source selection (see Terms and abbreviations)
Selects a binary source whose status is transmitted as bit 14 of 06.11
Main status word.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...