G-2 Ethernet/IP Setup
3AXD50000011888
Group 52 FBA A Data In (PLC Input Data)
(Note: that first three words back to PLC are pre-defined or already mapped for you.)
Main Status Word (MSW)
See status word bit description below
Actual Value 1
Speed (1=1rpm)
Actual Value 2
Torque (% of motor nominal x 100)
52.01 FBA A Data In1 = Parameter 1.07[16]
Motor Current (1=1Amp)
52.02 FBA A Data In2 = Parameter 1.11[16]
DC Bus Voltage x 10
52.03 FBA A Data In3 = Parameter 1.14[16]
Actual motor power in HP x 10
52.04 FBA A Data In1...
These additional data words could be used to read other parameters
from the drive.
52.10 FBA A Data In10
These additional data words could be used to read other parameters
from the drive.
(Note: the first three words sent to the drive are pre-defined or already mapped for you.)
Main Control Word (MCW)
See control word bit description below.
Speed Reference 1
Scaling is 1=1rpm
Reference 2
Not used in ACS880 CTDD
53.01 FBA A Data Out1 = Parameter 23.14[16]
Accel Time 2 (optional) These additional data words could be used to
write to other parameters within the drive.
For example, writing a value of 300 here would set par 23.12 Accel
Time 1 to 30 seconds.
53.04 FBA A Data Out1...
Up to 10 additional parameters can be mapped here for cyclic
updating.
53.10 FBA A Data Out10
Up to 10 additional parameters can be mapped here for cyclic
updating.
Last step after changing any fieldbus related parameters in Groups 50-53:
51.27 FBA A Par Refresh
Refresh Reboots fieldbus card so changes will take effect (or the drive
power can be cycled).
ACS880 CTDD Drive on EtherNet/IP FENA-21 or FEIP-21 with Studio 5000 Logix Designer® or RSLogix® 5000
1. Open Studio 5000 Logix Designer® or RSLogix® 5000 and open a new project.
2. Right click on the Ethernet module within the Controller Organizer window.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...