Startup Assistant & Parameters 12-51
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
STANDARD DIO,
FI, FO
(Continued)
DIO1 ON DELAY
(11.07)
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO1 (when used
as a digital output or digital input).
t
On
= 11.07
DIO1 ON delay
t
Off
= 11.08
DIO1 OFF delay
1
0
1
0
t
On
t
Off
t
On
t
Off
Time
*DIO status
*Delayed DIO status
*Electrical status of digital input. Indicatedc by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
DIO1 OFF DELAY
(11.08)
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input/output DIO1 (when used
as a digital output or digital input). See parameter 11.07 DIO1 ON
delay.
DIO2 FUNCTION
(11.09)
Default: Output (0)
Range: 0 - 2
Output (0) DIO2 is used as a digital output
Input (1) DIO2 is used as a digital input
Frequency (2) DIO2 is used as a frequency input
Selects whether DIO2 is used as a digital output or input, or a
frequency output.
DIO2 OUTPUT SOURCE
(11.10) Default: Running (7)
Range: 0 - 44, Other
Selects a drive signal to be connected to digital input/output DIO2
when parameter 11.09 DIO2 function is set to Output.
For the available selections, see parameter 11.06 DIO1 output source.
DIO2 ON DELAY
(11.11)
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the activation delay for digital input/output DIO2 (when used
as a digital output or digital input).
t
On
= 11.11
DIO2 ON delay
t
Off
= 11.12
DIO2 OFF delay
1
0
1
0
t
On
t
Off
t
On
t
Off
Time
*DIO status
*Delayed DIO status
*Electrical status of digital input. Indicatedc by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
DIO2 OFF DELAY
(11.12)
Default: 0.0 s
Range: 0.0 to 3000.0 s
Defines the deactivation delay for digital input/output DIO2 (when used
as a digital output or digital input). See parameter 11.11 DIO2 ON
delay.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...