12-28 Startup Assistant & Parameters
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
MAIN STATUS WORD
(06.11)
Default:
Read Only
Range: 0 - 15
Main status word of the drive. This parameter is read-only.
Bit
Name
Value
Description
0
Ready to
switch ON
1
Ready to switch ON
0
Not ready to switch ON
1
Ready run
1
Ready to operate
0
OFF1 active
2
Ready ref
1
Operation enabled
0
Operation inhibited
3
Tripped
1
Fault
0
No Fault
4
OFF2 inactive
1
OFF2 inactive
0
OFF2 active
5
OFF3 inactive
1
OFF3 inactive
0
OFF3 active
6
Switch-on
inhibited
1
Switch-on inhibited
0
--
7
Warning
1
Warning active
0
No warning active
8
At setpoint
1
Operating - Actual value equals
reference = is within
tolerance limits (see parameters
46.21 - 46.23)
0
Actual value differs from reference
= is outside tolerance
limits
9
Remote
1
Drive control location: Remote
(EXT1 or EXT2)
0
Drive control location: Local
10
Trickle Current
Active
0
Trickle Current OFF
1
Trickle Current ON
11
De-Ice Mode
Active
0
De-Ice Mode OFF
1
De-Ice Mode ON
12
CTD Run
0
CTD Drive Not Running
1
CTD Drive Running
13
CTD HOLD
0
CTD Autophase OFF
1
CTD Autophase ON
14
User bit 3
-
See parameter 06.33 MSW bit 14
sel
15
Reserved
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...