Ethernet/IP Setup G-1
3AXD50000011888
Appendix G
Ethernet/IP Setup
G.1 ACS880 Cooling Tower Drive
G.1.1 Ethernet/IP Setup
This document will guide you through the process of setting up the ACS880 Cooling Tower Drive for monitoring and control
over Ethernet/IP using the following data in and out:
Status Word
Control Word
Ref 1
Actual Speed (rpm)
Ref 2
% Motor Torque x 100
Accel Time
Motor Current (1=1Amp)
DC Bus Volts x 10
This guide assumes that the basic drive setup has already been done. This includes setting the Language & Units, entering
Motor Data and performing an ID Run.
Once this basic drive setup has been done, the following parameters will need to be set:
Group 76: CTD Motor Control
76.03 Operating Mode = FIELDBUS
96.02 Pass Code = 13 Fieldbus
Group 50: Fieldbus Adapter
50.01 FBA A Enable = Option Slot 1
This is the top option slot on the drive. Adapter can go in any slot
50.02 FBA A Comm Loss Function = Warning
This setting determines what the drive does when comms are lost
50.03 FBA A Comm Loss Timeout = 3sec
This time is added to the time in 51.20 before issuing a fault/warning
50.04 FBA A ref1 Type = Speed
50.08 FBA A Act1 Transparent source = Torque
50.09 FBA A SW Transparent Source = 6.11[16]
Status Word sent back to the PLC will be par 6.11 Main Status Word
Group 51: FBA A Settings (Ethernet Adapter Setup)
51.01 FBA A Type = EtherNet
51.02 Protocol/Profile = EIP T16 (102)
51.03 Comm Rate = Auto
Automatically adjusts to 10 or 100Mbit/s network speed
51.04 IP Configuration = STATIC
51.05 IP Address
ex. 192
51.06 IP Address
ex. 168
51.07 IP Address
ex. 3
51.08 IP Address
ex. 88
51.09 Subnet CIDR = 24
Shorthand for 255.255.255.0
51.10 GW Address
Leave at default (zero) if not used
51.11 GW Address
Leave at default (zero) if not used
51.12 GW Address
Leave at default (zero) if not used
51.13 GW Address
Leave at default (zero) if not used
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...