Startup Assistant & Parameters 12-5
3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
Highlight the motor value to be edited using
keys. Use to edit the values.
Use and to change the value of a digit. Use
and to move the curser left and right.
Press
(save) to enter the value.
PMSM
.
360.0 V
1.3 A
500 rpm
Motor Type
Back EMF voltage
Motor nominal current
Motor nominal speed
00:00
Next
Back
CTDD
50.0 rpm
Local
Motor data
Check the values from the motor’s
nameplate, and enter them here.
Important!
Motor Back EMF voltage (located on
the motor nameplate) is critical to the successful
operation of the cooling tower motor. Please record
this data here for future reference.
Back EMF Voltage:
Motor Serial Number:
Note:
Back EMF Voltage is referrred to as
Measured Open Circuit Voltage on the motor
nameplate.
000.
0
v
00:00
Save
Cancel
CTDD
0.0 rpm
Local
99.07
Motor Back EMF voltage
80.0
960.0
Motor ID Run
Autophasing
The drive is now ready to run the motor identification
routine (ID run). During the ID run, the motor is
injected with DC current. Autophase stops the rotor
prior to the ID run.
Note:
Autophase time has a default of 15 seconds.
It is best to observe the time it takes the fan to stop
moving and use this as an accurate autophase time.
Use the keys to move between selections.
Use to select the value to edit.
00:00
Back
50.0 rpm
Local
Autophasing
Select parameters for autophasing.
Autophasing Current
Next
50%
CTDD
Autophasing Time
15 S
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...