D-10 Mechanical Installation
3AXD50000011888
D.7.2 Frames R4 and R7 (UL Type 12)
1. Position the drive onto the screws on the wall as shown in section Frames R5 to R9 without vibration dampers on page
50.
2. Put the hood onto the upper screws.
3. Tighten the upper screws in the wall securely.
4. Tighten the lower screws in the wall securely.
Note:
Do not open or remove the cable entry box for easier installation. The gaskets do not fulfill the degree of protection if
the box is opened.
Figure D-11
D.7.3 Frames R5 and R9 without Vibration Dampers
1. See the dimensions in chapter Dimension drawings. Mark the locations for the four or six mounting holes.
2. Drill the mounting holes.
3. Start the screws or bolts into the mounting holes.
4. Remove the front cover.
5. For IP21 units: Attach the cable entry box to the drive frame. For instructions, see the assembly drawing in the cable
entry box. A view of frame R5 is shown below.
6. Position the drive onto the screws on the wall.
7. Tighten the accessible screws in the wall securely.
Note:
If you use the lower mounting screws, you can replace the drive module without unfastening the cable entry box.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...