ModbusTCP Setup E-5
3AXD50000011888
Now, let’s look at the Control Word bit structure. These are the bits we will turn on and off to control the drive:
Control Word Bit #
Function
Decimal number to write into
control word to turn this bit “ON”
0
Trickle Heating
1
1
De-Ice Mode
2
2
Start Forward
4
Turning a bit ON will cause that function to start. Only one function should be ON at a time.
So, let’s tell the drive to start and run at 100rpm:
Write a value of 100 to REF1 for the speed reference. (100rpm)
Set CW bit 2=1 by writing a decimal value of 4 to the CW. (drive should start)
Note!
If you have set par 53.01 = 23.12, then make sure to also write a value into register 40004 for the Accel Time 1.
Try “300” for 30 seconds. If left empty, Modbus Poll will write a value of zero into this parameter. An accel time of zero is
unreasonable and may cause a drive fault.
For the CTD firmware only, a few additional bits have been added to the Main Status Word (SW) in par 6.11:
Status Word Bit #
Function
10
Trickle Heating Active (on during delay and heating)
11
De-Ice Mode Active
12
CTDD Running (motor actually turning – ***not active in de-ice mode***)
13
CTDD Hold (autophasing in progress)
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...