Startup Assistant & Parameters 12-21
3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
WARNINGS
AND FAULTS
(Continued)
5TH LATEST WARNING
(04.20)
Default:
Read Only
Range: 0000h - FFFFh
Code of the 5th stored (non-active) warning.
EVENT WORD
(04.40)
Default:
Read Only
Range: 0000h - FFFFh
User-defined event word. This word collects the status of the events
(warnings, faults or pure events) selected by parameters 04.41 to
04.72.
For each event, an auxiliary code can optionally be specified for
filtering. This parameter is read-only.
Bit
Name
Description
0
User bit 0
1 = Event selected by parameters 04.41 (and
04.42) is active
1
User bit 1
1 = Event selected by parameters 04.43 (and
04.44) is active
---
---
---
15
User bit 15 1 = Event selected by parameters 04.71 (and
04.72) is active
EVENT WORD 1 BIT 0 CODE
(04.41)
Default: 0000h
Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 0 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 0 AUX
CODE
(04.42)
Default: 0000 0000h
Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 1 CODE
(04.43)
Default: 0000h
Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 1 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
EVENT WORD 1 BIT 1 AUX
CODE
(04.44)
Default: 0000 0000h
Range: 0000 0000h - FFFF FFFFh
Code of warning, fault or pure event. Specifies an auxiliary code for
the event selected by the previous parameter. The selected event is
indicated by the event word only if its auxiliary code matches the value
of this parameter.
With a value of 0000 0000h, the event word will indicate the event
regardless of the auxiliary code.
EVENT WORD 1 BIT 2 CODE
(04.45)
Default: 0000h
Range: 0000h - FFFFh
Code of event. Selects the hexadecimal code of an event (warning,
fault or pure event) whose status is shown as bit 2 of 04.40 Event word
1. The event codes are listed in chapter Fault tracing.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...