Control Wiring 6-5
3AXD50000011888
6.4 N5350 Relay Outputs
The N5350 has the ability of reporting multiple internal states to the user by the use of relay outputs. For example,
a relay can be set up to illuminate an external indicator light should the drive fault.
Three Form-C relay outputs are provided in the N5350.
The functions of the relay outputs are selected by parameters 10.24 RO1 Source, 10.27 RO2 Source and 10.30 RO3 Source.
For details on setting the Relay Output function see the ACS880 software manual.
Figure 6-3 depicts connections to the digital outputs for the various ways they can be used.
Figure 6-3 Relay Outputs
XR01, XR02, XR03
Relay outputs
1
2
3
1
2
3
1
2
NC
COM
NO
NC
COM
NO
NC
COM
3
NO
Ready
250 VAC / 30 VDC
2 A
Running
250 VAC / 30 VDC
2 A
Faulted (-1)
250 VAC / 30 VDC
2 A
Table 6-3 Relay Output Technical Data
Relay outputs RO1…RO3 (XRO1…XRO3)
Connector pitch 5mm, wire size 2.5mm
2
250VAC / 30VDC, 2A
Protected by varistors
+24V output (XD24:2 and XD24:4)
Connector pitch 5mm, wire size 2.5mm
2
Total load capacity of these outputs is 4.8W (200mA / 24V)
minus the power taken by DIO1 and DIO2.
Summary of Contents for ACS880+N5350
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 N5350 cooling tower drives User s guide ...
Page 32: ...Terminal Specifications 4 7 3AXD50000011888 Figure 4 3 Cable Conduit Installation R6 R7 R8 R9 ...
Page 193: ...13 20 Troubleshooting 3AXD50000011888 ...
Page 211: ...C 2 CE Guidelines 3AXD50000011888 Figure C 1 Declaration of Conformity ...
Page 212: ...CE Guidelines C 3 3AXD50000011888 ...
Page 246: ...Ethernet IP Setup G 5 3AXD50000011888 8 The ACS880 CTD Drive is now added to the PLC I O ...