248 Actual signals and parameters
2907 USER MWh
TRIG
Defines the trigger point for the drive power consumption
counter. Value is compared to parameter
value.
0.0 MWh
0.0…
6553.5 MWh
Megawatt hours. If parameter value is set to zero, the trigger
is disabled.
1 =
0.1 MWh
2908 USER MWh
ACT
Defines the actual value of the drive power consumption
counter. When parameter
has been
set to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by
parameter
, a maintenance notice is displayed on the
panel.
0.0 MWh
00.0…
6553.5 MWh
Megawatt hours. Parameter is reset by setting it to zero.
1 =
0.1 MWh
30 FAULT
FUNCTIONS
Programmable protection functions
3001 AI<MIN
FUNCTION
Defines the drive response if the analog input (AI) signal
drops below the fault limits and AI is used
• as the active reference source (group
• as the process or external PID controllers' feedback or
,
) and the
corresponding PID controller is active.
and
set the
fault limits.
NOT SEL
Protection is inactive.
0
FAULT
and the motor coasts to stop. Fault limit is defined by
parameter
/
1
CONST SP 7
The drive generates alarm
(
(
) and sets the speed to the value defined by
parameter
. Alarm limit is defined by
parameter
/
WARNING!
Make sure that it is safe to continue
operation in case the analog input signal is lost.
2
LAST SPEED
The drive generates alarm
(
(
) and freezes the speed to the level the drive was
operating at. The speed is determined by the average
speed over the previous 10 seconds. Alarm limit is defined
by parameter
/
.
WARNING!
Make sure that it is safe to continue
operation in case the analog input signal is lost.
3
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...