Actual signals and parameters 203
CS1/2/3/4
When parameter
, this timed function selects a
constant speed. 1 = timed function active, 0 = timed
function inactive.
, timed functions 1 and 2 select a constant speed.
1 = timed function active, 0 = timed function inactive.
2
13 ANALOG INPUTS
Analog input signal processing
1301 MINIMUM AI1
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI1. When used as a
reference, the value corresponds to the reference minimum
setting.
0…20 mA 0…100%
4…20 mA 20…100%
-10…10 mA -50…50%
Example:
If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter
.
Note:
value must not exceed
value.
1.0%
-100.0…100.0% Value as a percentage of the full signal range.
Example:
If the minimum value for analog input is 4 mA, the
percentage value for 0…20 mA range is:
(4 mA / 20 mA) · 100% = 20%
1 = 0.1%
All parameters
No.
Name/Value
Description
Def/FbEq
Timed function 1…4 Operation
0
1
Timed
function 1
Timed
function 2
Operation
0
0
1
0
0
1
1
1
=
=
=
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...