Appendix: Safe torque off (STO) 429
•
32 °C board temperature at 2.0% of time
•
60 °C board temperature at 1.5% of time
•
85 °C board temperature at 2.3% of time.
• The STO is a type A safety component as defined in IEC 61508-2.
• Relevant failure modes:
•
The STO trips spuriously (safe failure)
•
The STO does not activate when requested
A fault exclusion on the failure mode “short circuit on printed circuit board” has
been made (EN 13849-2, table D.5). The analysis is based on an assumption that
one failure occurs at one time. No accumulated failures have been analyzed.
• STO reaction time (shortest detectable break): 10 microseconds
• STO response time: 2 ms (typical), 5 ms (maximum)
• Fault detection time: Channels in different states for longer than 200 ms
• Fault reaction time: Fault detection time + 10 ms
• STO fault indication (parameter 3025) delay: < 200 ms
• STO warning indication (parameter 3025) delay: < 200 ms
• Maximum cable length 300 m (984 ft) between activation switch (K) and drive
control unit.
• The voltage at the INx terminals of each drive must be at least 13 V DC to be
interpreted as “1”.
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...