158 Program features
It is also possible to monitor motor temperature by connecting a PTC sensor and
a thermistor relay between the +24 V DC voltage supply offered by the drive and a
digital input. The figure below displays the connection.
WARNING!
According to IEC 60664, the connection of the motor thermistor to
the digital input requires double or reinforced insulation between motor live
parts and the thermistor. Reinforced insulation entails a clearance and creeping
distance of 8 mm (0.3 in) (400/500 V AC equipment).
If the thermistor assembly does not fulfill the requirement, the other I/O terminals of
the drive must be protected against contact, or a thermistor relay must be used to
isolate the thermistor from the digital input.
Settings
Diagnostics
Parameter
Additional information
Group
Analog input settings
Group
Analog output settings
Group
Motor temperature measurement settings
Other
At the motor end the cable shield should be grounded through, eg, a 3.3 nF capacitor. If this is
not possible, the shield is to be left unconnected.
Actual signal
Additional information
Motor temperature
Alarm/Fault
Additional information
Excessive motor temp
T
Thermistor
relay
DI1…5
+24 V DC
Motor
Par.
=
or
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...