Actual signals and parameters 253
3010 STALL
FUNCTION
Selects how the drive reacts to a motor stall condition. The
protection wakes up if the drive has operated in a stall
region (see the figure below) longer than the time set by
parameter
In vector control the user defined limit =
(applies for positive
and negative torques).
In scalar control the user defined limit =
.
The control mode is selected by parameter
NOT SEL
Protection is inactive.
0
FAULT
The drive trips on fault
) and the
motor coasts to stop.
1
ALARM
The drive generates alarm
).
2
3011 STALL
FREQUENCY
Defines the frequency limit for the stall function. See
parameter
.
20.0 Hz
0.5…50.0 Hz
Frequency
1 = 0.1 Hz
3012 STALL TIME
Defines the time for the stall function. See parameter
.
20 s
1…400 s
Time
1 = 1 s
3013 UNDERLOAD
FUNC
Selects how the drive reacts to underload. The protection
wakes up if:
• the motor torque falls below the curve selected by
parameter
,
• output frequency is higher than 10% of the nominal motor
frequency and
• the above conditions have been valid longer than the time
NOT SEL
Protection is inactive.
0
All parameters
No.
Name/Value
Description
Def/FbEq
Torque (%) /
Current
(A)
0.95
·
User defined limit
Stall region
Par.
f
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...