366 Fault tracing
1017
PAR SETUP 1
(6320)
bit 15
Only two of the following
can be used
simultaneously: MTAC-
01 pulse encoder
interface module,
frequency input signal or
frequency output signal.
Disable frequency output, frequency
input or encoder:
• change transistor output to digital
mode (value of parameter
= 0 [
]), or
• change frequency input selection to
other value in parameter groups
and
, or
) and remove
MTAC-01 pulse encoder interface
module.
CODE FAULT
CAUSE
WHAT TO DO