Control panels 77
Overview
The following table summarizes the key functions and displays on the basic control
panel.
No. Use
1
LCD display – Divided into five areas:
a. Upper left – Control location:
LOC: drive control is local, that is, from the
control panel
REM: drive control is remote, such as the drive
I/O or fieldbus.
b. Upper right – Unit of the displayed value.
c. Center – Variable; in general, shows parameter
and signal values, menus or lists. Shows also
fault and alarm codes.
d. Lower left and center – Panel operation state:
OUTPUT: Output mode
PAR: Parameter mode
MENU: Main menu.
: Fault mode.
e. Lower right – Indicators:
FWD (forward) / REV (reverse): direction of the motor rotation
Flashing slowly: stopped
Flashing rapidly: running, not at setpoint
Steady: running, at setpoint
: Displayed value can be modified (in the Parameter and Reference modes).
2
RESET/EXIT – Exits to the next higher menu level without saving changed values.
Resets faults in the Output and Fault modes.
3
MENU/ENTER – Enters deeper into menu level. In the Parameter mode, saves the
displayed value as the new setting.
4
Up –
• Scrolls up through a menu or list.
• Increases a value if a parameter is selected.
• Increases the reference value in the Reference mode.
• Holding the key down changes the value faster.
5
Down –
• Scrolls down through a menu or list.
• Decreases a value if a parameter is selected.
• Decreases the reference value in the Reference mode.
• Holding the key down changes the value faster.
6
LOC/REM – Changes between local and remote control of the drive.
7
DIR – Changes the direction of the motor rotation.
8
STOP – Stops the drive in local control.
9
START – Starts the drive in local control.
2
3
4
6
7
8
9
1b
1e
1a
1d
5
LOC
A
OUTPUT
FWD
11
.
1c
FAULT
SET
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...