326 Fieldbus control with embedded fieldbus
Note:
Parameter writes through standard Modbus are always volatile, ie, modified
values are not automatically stored to the permanent memory. Use parameter
to save all changed values.
Function codes
Supported function codes for the holding 4xxxx register:
Note:
In the Modbus data message, register 4xxxx is addressed as xxxx -1. For
example, register 40002 is addressed as 0001.
40034 ACS355 Status
word MSW
R
, ie, the most significant word of
the DCU profile 32-bit Status word.
Supported only by the DCU profile, ie, when
Code
hex
(dec)
Function name
Additional information
03
(03)
Read 4X Register Reads the binary contents of registers (4X references) in a slave
device.
06
(06)
Preset single 4X
register
Presets a value into a single register (4X reference). When
broadcast, the function presets the same register reference in all
attached slaves.
10
(16)
Preset multiple
4X registers
Presets values into a sequence of registers (4X references). When
broadcast, the function presets the same register references in all
attached slaves.
17
(23)
Read/Write 4X
registers
Performs a combination of one read operation and one write
operation (function codes 03 and 10) in a single Modbus
transaction. Write operation is performed before the read
operation.
Modbus register
Access Information
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...