Actual signals and parameters 231
2109 EMERG STOP
SEL
Selects the source for the external emergency stop
command.
The drive cannot be restarted before the emergency stop
command is reset.
Note:
The installation must include emergency stop devices
and any other safety equipment that may be needed.
Pressing the stop key on the drive’s control panel does
NOT:
• generate an emergency stop of the motor
• separate the drive from dangerous potential.
NOT SEL
Emergency stop function is not selected
0
DI1
Digital input DI1. 1 = stop along the emergency stop ramp.
See parameter
. 0 = emergency
stop command reset.
1
DI2
See selection
.
2
DI3
See selection
.
3
DI4
See selection
.
4
DI5
See selection
.
5
DI1(INV)
Inverted digital input DI. 0 = stop along the emergency stop
ramp. See parameter
. 1 =
emergency stop command reset
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
DI4(INV)
See selection
.
-4
DI5(INV)
See selection
.
-5
2110 TORQ BOOST
CURR
Defines the maximum supplied current during torque boost.
See parameter
.
100%
15…300%
Value as a percentage
1 = 1%
2111 STOP SIGNAL
DLY
Defines the stop signal delay time when parameter
is set to
0 ms
0…10000 ms
Delay time
1 = 1 ms
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...