Actual signals and parameters 215
1611 PARAMETER
VIEW
Selects the parameter view, ie, which parameters are
shown.
Note:
This parameter is visible only when it is activated by
the optional FlashDrop device. FlashDrop is designed for
fast copying of parameters to unpowered drives. It allows for
easy customization of the parameter list, eg, selected
parameters can be hidden. For more information, see
MFDT-01 FlashDrop user’s manual
(3AFE68591074
[English]).
FlashDrop parameter values are activated by setting
parameter
to 31 (
DEFAULT
Complete long and short parameter lists
0
FLASHDROP
FlashDrop parameter list. Does not include short parameter
list. Parameters which are hidden by the FlashDrop device
are not visible.
1
1612 FAN
CONTROL
Selects the fan to be switched on and off automatically or
keeps the fan on all the time.
When the drive is used in ambient temperatures of 35 °C
(95 °F) and above, it is recommended to have the cooling
fan always on (selection
AUTO
Automatic fan control. The fan is switched on when the drive
is modulating. After the drive has stopped, the fan stays on
until the temperature of the drive has dropped below 55 °C
(131 °F). The fan then remains switched off until either the
drive is started or the temperature increases above 65 °C
(149 °F).
If the control board is powered from an external 24 V power
supply, the fan is switched off.
0
ON
Fan always on
1
1613 FAULT RESET Resets the current fault.
DEFAULT
No reset done. Current status continues.
0
RESET NOW
Resets the current fault. After reset, the parameter value
returns to DEFAULT.
1
18 FREQ IN & TRAN
OUT
Frequency input and transistor output signal processing.
1801 FREQ INPUT
MIN
Defines the minimum input value when DI5 is used as a
frequency input. See section
on page
.
0 Hz
0…16000 Hz
Minimum frequency
1 = 1 Hz
1802 FREQ INPUT
MAX
Defines the maximum input value when DI5 is used as a
frequency input. See section
on page
.
1000 Hz
0…16000 Hz
Maximum frequency
1 = 1 Hz
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...