Actual signals and parameters 257
3029 FAULT RAMP
STOP
Enables the emergency ramp stop when the drive faults.
0
DISABLE
Coast stop used.
0
ENABLE
Fault ramp stop enabled. The drive stops using an
emergency ramp when a non-critical fault occurs.
The following critical faults will always cause the coast stop
regardless of the value of this parameter:
• 0001 OVERCURRENT
• 0002 DC OVERVOLT
• 0004 SHORT CIRC
• 0044 SAFE TORQUE OFF
• 0045 STO1 LOST
• 0046 STO2 LOST.
1
31 AUTOMATIC
RESET
Automatic fault reset. Automatic resets are possible only for
certain fault types and when the automatic reset function is
activated for that fault type.
3101 NUMBER OF
TRIALS
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
If the number of automatic resets exceeds the set number
(within the trial time), the drive prevents additional automatic
resets and remains stopped. The drive must be reset from
the control panel or from a source selected by parameter
Example:
Three faults have occurred during the trial time
defined by parameter
. Last fault is reset only if the
is 3 or more.
0
0…5
Number of the automatic resets
1 = 1
3102 TRIAL TIME
Defines the time for the automatic fault reset function. See
parameter
.
30.0 s
1.0…600.0 s
Time
1 = 0.1 s
3103 DELAY TIME
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
. If delay time is set to zero, the drive
resets immediately.
0.0 s
0.0…120.0 s
Time
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq
X
X X
t
Trial time
X = Automatic reset
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...