324 Fieldbus control with embedded fieldbus
Actual value scaling
The scaling of the integers sent to the master as Actual values depends on the
selected function. See chapter
on page
Modbus mapping
The following Modbus function codes are supported by the drive.
Function
Code
hex (dec)
Additional information
Read Multiple
Holding
Registers
03 (03)
Reads the contents of registers in a slave device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Write Single
Holding
Register
06 (06)
Writes to a single register in a slave device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Diagnostics
08 (08)
Provides a series of tests for checking the communication between
the master and the slave devices, or for checking various internal
error conditions within the slave.
The following subcodes are supported:
00 Return Query Data: The data passed in the request data field is
to be returned in the response. The entire response message
should be identical to the request.
01 Restart Communications Option: The slave device serial line
port must be initialized and restarted, and all of its communication
event counters cleared. If the port is currently in Listen Only Mode,
no response is returned. If the port is not currently in Listen Only
Mode, a normal response is returned before the restart.
04 Force Listen Only Mode: Forces the addressed slave device to
Listen Only Mode. This isolates it from the other devices on the
network, allowing them to continue communicating without
interruption from the addressed remote device. No response is
returned. The only function that will be processed after this mode
is entered is the Restart Communications Option function
(subcode 01).
Write Multiple
Holding
Registers
10 (16)
Writes to the registers (1 to approximately 120 registers) in a slave
device.
Parameter sets, control, status and reference values are mapped
as holding registers.
Read/Write
Multiple
Holding
Registers
17 (23)
Performs a combination of one read operation and one write
operation (function codes 03 and 10) in a single Modbus
transaction. The write operation is performed before the read
operation.
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...