116 Application macros
Torque control macro
This macro provides parameter settings for applications that require torque control of
the motor. Control can also be switched to speed control using a digital input. To
enable the macro, set the value of parameter
to 8 (
For the parameter default values, see section
Default values with different macros
page
. If you use other than the default connections presented below, see section
.
Default I/O connections
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Motor speed reference (Speed)
: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Motor torque reference (Torque)
: 4…20 mA
4)
6
GND
Analog input circuit common
7
AO
Motor speed value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1) (Speed)
13 DI2
Forward (0) / Reverse (1)
1)
14 DI3
Speed (0) / Torque (1) control selection
15 DI4
Constant speed 1
: parameter
16 DI5
Acceleration and deceleration selection
2)
X1B
17 ROCOM
Relay output 1
No fault [Fault (-1)]
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
max. 500 ohm
1…10 kohm
3)
1)
Speed control:
Changes rotation direction.
Torque control:
Changes torque direction.
2)
0 = ramp times according to parameters
.
1 = ramp times according to parameters
.
3)
360 degree grounding under a clamp.
4)
The signal source is powered externally. See the
manufacturer’s instructions. To use sensors
supplied by the drive aux. voltage output, see page
Tightening torque: 0.4 N·m / 3.5 lbf·in.
Safe torque off connections (X1C:STO; not shown in
the diagram) are jumpered by default.
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...