Appendix: Resistor braking 407
WARNING!
Never use a brake resistor with a resistance below the minimum
value specified for the particular drive. The drive and the internal chopper are
not able to handle the overcurrent caused by the low resistance.
Selecting the brake resistor cables
Use a shielded cable with the conductor size specified in section
. The maximum length of the resistor cable(s) is 5 m (16 ft).
3-phase
U
N
= 380
…
480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A2-4 200 1180
0.37
0.5
90
03x-01A9-4 175
800
0.55
0.75
90
03x-02A4-4 165
590
0.75
1
60
03x-03A3-4 150
400
1.1
1.5
37
03x-04A1-4 130
300
1.5
2
27
03x-05A6-4 100
200
2.2
3
17
03x-07A3-4
70
150
3.0
4
29
03x-08A8-4
70
110
4.0
5
20
03x-12A5-4
40
80
5.5
7.5
15
03x-15A6-4
40
60
7.5
10
10
03x-23A1-4
30
40
11
15
10
03x-31A0-4
16
29
15
20
16
03x-38A0-4
13
23
18.5
25
13
03x-44A0-4
13
19
22.0
30
10
1)
E =EMC filter connected (metal EMC filter screw installed),
U=EMC filter disconnected (plastic EMC filter screw installed), US
parametrization.
2)
CBR-V / CBT-H resistor types available in selected countries.
3)
Braking time = maximum allowed braking time in seconds at
P
BRmax
every 120 seconds, at 40 °C (104 °F) ambient temperature.
00353783.xls K
Symbols
R
min
= minimum allowed brake resistor that can be connected to the brake chopper
R
max
= maximum allowed brake resistor that allows
P
BRmax
P
BRmax
= maximum braking capacity of the drive, must exceed the desired braking power.
Ratings by resistor type
CBR-V
CBR-V
CBR-V
CBR-V
CBR-V
CBT-H
160
210
260
460
660
560
Nominal power (W)
280
360
450
790
1130
2200
Resistance (ohm)
70
200
40
80
33
18
Type
R
min
R
max
P
BRmax
Selection table by resistor type
ACS355-
CBR-V / CBT-H
2)
Braking time
3)
x = E/U
1)
ohm ohm
kW
hp
160 210 260 460 660 560
s
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...