378 Technical data
Alternate short-circuit protection
You can use the ABB Type E manual motor protectors MS132 & S1-M3-25, MS165-
xx and MS5100-100 as an alternate to the recommended fuses as a means of branch
circuit protection. This is in accordance with the National Electrical Code (NEC).
When the correct ABB Type E manual motor protector is selected from the table and
used for branch circuit protection, the drive is suitable for use in a circuit capable of
delivering no more than 65 kA RMS symmetrical amperes at the drive’s maximum
rated voltage. See the following table for the appropriate ratings. See the MMP rating
table for the minimum enclosure volume of IP20 open type ACS355 mounted in an
enclosure.
Drives with and without NEMA 1 enclosure kits are included in the UL file. The MMP
selections in the table are also valid for drives having a NEMA 1 enclosure kit
installed.
3-phase
U
N
= 380
…
480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A2-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-01A9-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-02A4-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-03A3-4
10
10
2.5
12
0.75
18
2.5
12
2.5
12
03x-04A1-4
16
15
2.5
12
0.75
18
2.5
12
2.5
12
03x-05A6-4
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-07A3-4
16
20
2.5
12
1.5
14
2.5
12
2.5
12
03x-08A8-4
20
25
2.5
12
2.5
12
2.5
12
2.5
12
03x-12A5-4
25
30
6
10
6
10
6
10
2.5
12
03x-15A6-4
35
35
6
8
6
8
6
8
2.5
12
03x-23A1-4
50
50
10
8
10
8
10
8
6
10
03x-31A0-4
80
80
16
6
16
6
16
6
10
8
03x-38A0-4
100
100
16
4
16
4
16
4
10
8
03x-44A0-4
100
100
25
4
25
4
16
4
10
8
1)
If 50% overload capacity is needed, use the larger fuse alternative.
00353783.xls L
Type
Fuses
Size of copper conductor in cablings
ACS355-
gG
UL Class
T or CC
(600 V)
Supply
(U1, V1, W1)
Motor
(U2, V2, W2)
PE
Brake
(BRK+, BRK-)
x = E/U
A
A
mm
2
AWG mm
2
AWG mm
2
AWG mm
2
AWG
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...