![ABB ACS355 series User Manual Download Page 174](http://html.mh-extra.com/html/abb/acs355-series/acs355-series_user-manual_2968174.webp)
174 Program features
ST1: Drive is started in forward direction with AI1 (AI1 + 50% - 50%) reference and
ramp pair 2. State shifts to the next state when reference is reached. All relay and
analog outputs are cleared.
ST2: Drive is accelerated with AI1 + 15% (AI1 + 65% - 50%) reference and 1.5 s
ramp time. State shifts to the next state when reference is reached. If reference is not
reached within 2 s, state shifts to state 8 (error state).
ST3: Drive is decelerated with AI1 + 10% (AI1 + 60% - 50%) reference and 0 s ramp
time
1)
. State shifts to the next state when reference is reached. If reference is not
reached within 0.2 s, state shifts to state 8 (error state).
ST4: Drive is decelerated with AI1 - 15% (AI1 + 35% -50%) reference and 1.5 s ramp
time. State shifts to the next state when reference is reached. If reference is not
reached within 2 s, state shifts to state 8 (error state).
2)
ST5: Drive is accelerated with AI1 -10% (AI1 + 40% -50%) reference and 0 s ramp
time
1)
. State shifts to the next state when reference is reached. Sequence counter
value is increased by 1. If sequence counter elapses, state shifts to state 7 (sequence
completed).
ST6: Drive reference and ramp times are the same as in state 2. Drive state shifts
immediately to state 2 (delay time is 0 s).
ST7 (sequence completed): Drive is stopped with ramp pair 1. Digital output DO is
activated. If Sequence programming is deactivated by the falling edge of digital input
DI1, state machine is reset to state 1. New start command can be activated by digital
input DI1 or by digital inputs DI4 and DI5 (both inputs DI4 and DI5 must be
simultaneously active).
ST8 (error state): Drive is stopped with ramp pair 1. Relay output RO is activated. If
Sequence programming is deactivated by the falling edge of digital input DI1, state
machine is reset to state 1. New start command can be activated by digital input DI1
or by digital inputs DI4 and DI5 (both inputs DI4 and DI5 must be simultaneously
active).
1)
0 second ramp time = drive is accelerated/decelerated as rapidly as possible.
2)
State reference must be between 0…100%, ie, scaled AI1 value must be between
15…85%. If AI1 = 0, reference = 0% + 35% -50% = -15% < 0%.
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...